- Sara Aagesen, Spainโs ecological transition minister, has presented a report on the Aprilโฏ28 electricity crisis, identifying a multifactorial origin for its grid collapsing. ย ย
- She said three main factors pushed the system past a โpoint of no returnโ: insufficient voltage control capacity, fluctuations due to system constraints, and generation disconnections she described as โapparently improper.โ
In other words, voltage was not regulated due to poor planning by the system operator, and several generators failed to perform as required.
Aagesen detailed several anomalies in the electrical system on Aprilโฏ27 and the morning of the blackout. โThere was already instability from nine in the morning,โ she said, adding that โvarious calls were made from the control centers.โ
But on the day of the incident, she explained, the outage was triggered by โa phenomenon of overvoltages, a chain reaction, and generation disconnections that in turn caused further disconnections.โ
Voltage control
On one hand, the system lacked sufficient dynamic voltage control capacity.
โThe generation units that should have controlled voltage did not absorb all the reactive power that was expected in a context of high voltages,โ she said, referring to synchronous generation plants โ nuclear and hydroelectric โ and combined cycle plants, which failed to absorb voltage as expected and contributed to the overvoltage.
โThe thermal generation units that should have controlled voltage, and which are financially compensated for doing so, did not absorb the power,โ noted Spanish PV association UNEF. โAll the reactive power that was expected in a context of high voltages.โ
The second factor involved system oscillations. The operator applied corrective measures, but those actions increased system stress.
Aagesen said grid operator Red Elรฉctrica de Espaรฑa (REE) had โsufficient generation capacity to respond.โ โBut the electricity system operator did not schedule the day before all the generation necessary to control an overvoltage episode.โ
Third, generators disconnected as sustained high voltage before the blackout caused safety trips. At 12:33โฏp.m. (CEST), several generating plants tripped out of the acceptable operating range, said Aagesen.
Missing data
The minister said she regretted that the report did not include all information requested from the parties involved. ENTSO-E previously flagged this shortfall in a letter to her.
She also announced a Royal DecreeโLaw package of 11 measures to control voltage โ eight related to system operation and three to strengthen cybersecurity.
โThere is no evidence of a cyberattack,โ she explained. โHowever, vulnerabilities have been identified that could expose networks or systems to potential future risks โฆ This report should be understood as an analytical tool and, above all, as a tool for action. An opportunity to strengthen what works and review what can be improved.โ
UNEF noted that photovoltaic technology can already control voltage, but current regulations prevent its use for that purpose.
โFrom the photovoltaic sector, we positively value the announcement made today by Minister Sara Aagesen that the approval of the Operationโฏ7.4 procedure will be accelerated, which will allow photovoltaic technology to contribute to controlling grid voltage,โ said the Spanish PV association. โIt is also time to accelerate the implementation of other technologies already available and that are key to maintaining stable voltage levels, managing variability, and ensuring energy security based on renewable energy, such as gridโforming inverters (pending approval by European regulations) and storage.
Author: Pilar Sรกnchez Molina