- The Energy Systems Integration Group has published aย studyย on the benefits of grid-forming battery energy storage systems (GFM BESS).
- The study is based on research conducted by ESIGโs GFM BESS project team, which evaluated GFM BESS benefits on an actual transmission network.
ESIG explains that GFM controls can provide grid-stabilizing characteristics that support the reliable operation of a power system under increasing levels of inverter-based resources (IBR), such as solar and wind power. While โGFM controls can be implemented on new solar photovoltaic and wind plants, with some limitations,โ ESIG says, battery energy storage is โparticularly low-hanging fruitโ for the implementation of GFM controls.
Solar, wind and storage without GFM controls use grid-following (GFL) inverters.
The project team found that using GFM BESS instead of GFL BESS in a transmission system improves the hosting capacity for solar and wind generators.
The team reached that conclusion by studying a portion of an actual transmission networkโa weak local area with limited transmission that is โsaturatedโ with 780 MW of PV generation capacity using GFL inverters, paired with 225 MW of GFL BESS. While in the real world, that weak local area is actually connected to a strong surrounding transmission network, the researchers modeled the local area in isolation in order to model โthe weakest grid conditions possible.โ
They found that in the weak local area, which would have been โmarginally stableโ on its own, substituting GFM BESS for the 225 MW of GFL BESS would enable an additional 125 MW of PV with GFL inverters, โdemonstrating that increased IBR hosting capacity was obtained before hitting a stability limit.โ
The team reported that GFL BESS has a โsmall incremental costโ above that of GFL BESS โwhen designed-in up front,โ and has a โdramatically lower cost than other solutionsโ such as synchronous condensers.
The study recommended, among other steps, that transmission system operators consider adopting GFM BESS โsystem-wide to improve stability and to maximize IBR [instant backup recovery]hosting capacity.โ
Another study recommendation is to develop GFM BESS technical requirements and integrate those requirements into facility interconnection requirements.
โDonโt wait,โ the study says. โTake advantage of BESS interconnections todayโ because โretrofits are expensive.โ
Among other key findings, the study said that GFM BESS isย a โDo No Harmโ solution, in part because it provides specific stability benefits in weaker grids and operates stably and reliably in strong grids.
In addition, it found that GFM BESS systems are interoperable across original equipment manufacturers and with GFL inverters; can help defer other more costly solution options; and can serve as a bridge to long lead-time solutions.
The project team plans to publish a brief on the benefits of GFM BESS for decision makers, policymakers and regulators, and to conduct outreach to key stakeholders.
The project teamโs core modelling and study team efforts were conducted by Elevate Energy Consulting, Electranix Corporation, and ESIG, in partnership with the utility American Transmission Company.
Link to the full study HEREย